Opis
Can be used for basic or additional protection of persons against electric shock (I≤n ≤ 30 mA), for additional fault protection (IΔn> 30 mA) or for protection of property against fire (IΔn ≤ 300 mA). Rated conditional short-circuit resistance 6 kA. The network connection side is arbitrary – input / output terminals can be selected. The function of the device is not position dependent. Off-on status indication. Dual clamp function – head / yoke. The use of a 4-pole protector can also be used as 2-pole or 3-pole. The test button T must be activated once a month. Conductor cross-section 1.5–35 mm2. Surge Current Resistance 250 A. AC Type – AC residual current sensitivity. No equipment delay – shock current resistance of 250 A.
Properties:
– Number of poles: 4
– Rated voltage: 400 V
– Rated current: 25 A
– Selective type: No.
– Short circuit resistance (Icw): 6 kA
– Optional equipment: Yes
– Size (according to DIN 43880): 1
– Number of modules in one row: 4
– Type with short delay: No.
– Mounting depth: 69.5 mm
– Rated leakage current: 0.03 A
– Surge current resistance: 0.25 kA
– IP rating: IP20
– Mounting type: DIN rail
– Leakage current type: AC
– Frequency: 50 Hz
– Width: 70 mm
– Length: 80 mm
– Height: 71 mm
– Weight: 320 g